Insert: Work Performed Issues Found Parts Used Time On-Site
Replaced faulty capacitor on compressor board (unit A-12) Cleaned evaporator coils — heavy dust accumulation removed Topped up refrigerant to spec (R-410A, 2.4 lbs) Tested thermostatic expansion valve — operating within range Cycled system through 3 full heating/cooling sequences post-repair Access panel screws corroded — required extraction kit Secondary drain line partially blocked by debris Wiring insulation on compressor harness showing signs of heat stress Heat stress on wiring harness may indicate recurring overload condition — recommend electrical audit within 30 days. Part Code Description Qty Unit CAP-40/5-440 Dual Run Capacitor 40/5 MFD 1 ea REF-R410A R-410A Refrigerant 2.4 lbs FLT-20X25 Air Filter 20x25x1 MERV-11 2 ea DRAIN-CLR Condensate Drain Tabs 6 tabs
Schedule full electrical system audit — wiring harness concern Consider preventive coil cleaning contract (bi-annual) Replace drain pan — hairline crack detected, risk of moisture damage Upgrade to smart thermostat for better compressor cycle management Electrical audit booking — customer to confirm preferred date Drain pan replacement quote pending supplier response Customer requested 6-month maintenance visit reminder Low AI confidence on follow-up items — please verify action owners and due dates before saving. Save Note Discard Clear